Single Tariff Meter Configuration |
Optional Multi-Tariff Meter configuration |
| Specifications |
IEC Class 1.0 Energy Meter with DIN attachment and Power Connections |
IEC Class 1.0 Energy Meter with DIN attachment and Power Connections |
| Power |
3 X 65/80 A, 3 X 200 – 240 VAC 50 Hz, Single Phase, Two-Wire. DIN-standard base terminals. Active Power, Demand, Voltage and Current Readings. |
3 X 65/80 A, 3 X 200 – 240 VAC 50 Hz, Single Phase, Two-Wire. DIN-standard base terminals. Active Power, Demand, Voltage and Current Readings. |
| Stand-Alone Capability |
GSM functionality depends on at least one phase operating. |
Meter controls and display operational without any external power. Network Interfaces operate without system power. GSM functionality depends on at least one phase operating. |
| Multi-Tariff |
- |
Eight Tariffs and computation of Demand |
| Time of Use |
- |
Interval Recording of Energy Usage Per Phase for up to 3 Months with intervals from 15 minutes to 24 hours |
| Pulse Output |
SO pulse output with Kh of 1,000 or 3200 impulses per kWh |
SO pulse output with Kh of 1,000 or 3200 impulses per kWh |
| AC Voltage Monitor |
Meter calculates instantaneous AC RMS voltage on all phases. This can be read by the customer at any time. Alternately it can be sent in the AMR message |
Meter calculates instantaneous AC RMS voltage on all phases. This can be read by the customer at any time. Alternately it can be sent in the AMR message |
| Display |
Wide Temperature range (-40 to +70 Degrees Celsius), 8 digits with programmable decimal, annunciator for function and phase status |
Wide Temperature range, 8 digits with programmable decimal, annunciator for function and phase status |
| Power Fail Battery Operation |
No |
Optional |
| Environment |
-25 to +55 Degrees Celsius operating; -40 to +70 Degrees Celsius Storage, Humidity 0 – 100 percent, non-condensing, Altitude to 4,000 meters. IP51 housing for indoors use. |
-25 to +55 Degrees Celsius operating; -40 to +70 Degrees Celsius Storage, Humidity 0 – 100 percent, non-condensing, Altitude to 4,000 meters. IP54 housing for indoors or rain tight outdoor use. |
| Optical I/O |
IEC 601103 Mode C at 300 - 9600 baud |
IEC 601103 Mode C at 300 - 9600 baud |
| Serial I/O |
Internal TTL Serial I/O |
Optional RS-485 Isolated Serial Communications; 9.6 – 116 kBaud |
| Network |
SMS GPRS GSM |
Ethernet, Fiber Optic, GSM Interface Adaptors mounted within the meter enclosure |
| Pushbuttons |
- |
Dual Hermetic |
| Burden |
Without GSM Power Supply less than 1.5 VA, less than 0.5 VA per phase |
Without GSM Power Supply less than 1.5 VA, less than 0.5 VA per phase |
| Mechanical |
140 x 91.5 x 59.75 mm with DIN Rail attachment. Wire and Pin attachment at 13.5 mm from wall. |
140 x 60 x 25 mm IEC |
| Surge and Immunity to ESD |
To IEC 601036, with extended specifications to common Scandinavian requirements available as NC Option |
To IEC 601036, with extended specifications to common Scandinavian requirements available as NC Option |